Product Description
ÖLFLEX® CLASSIC 110 CY
ÖLFLEX® CLASSIC 415 CP
ÖLFLEX® TRAY II CY
Wide application range due to multiple approvals; Cost-saving, easy installation due to omission of closed raceways (suitable for open wiring)
- Torsion resistant for drip loops
- Broad application range (NFPA 70/NEC), NFPA 79 compliance, Outdoor use
- EMC/Screened
SKU: 100000027
Categories: CABLES & ACCESSORIES, Power and control cables, PVC sheath - approved, Various applications
Article List
Product description
Technical Data
Lapp No. | Product Name | Datasheet / Product video | Request Quote | ||||||
---|---|---|---|---|---|---|---|---|---|
Number of cores and mm² per conductor | AWG per conductor | Outer diameter (mm) | Copper index (kg/km) | Weight (kg/km) | |||||
ÖLFLEX® Tray II CY | |||||||||
Lapp 2218030 | ÖLFLEX TRAY II CY 3 G 1,0 | ||||||||
3 G 1,0 | 8,2 | 35.1 | 119 | ||||||
Lapp 2218040 | ÖLFLEX TRAY II CY 4 G 1,0 | ||||||||
4 G 1,0 | 8,8 | 55.2 | 137 | ||||||
Lapp 2218050 | ÖLFLEX TRAY II CY 5 G 1,0 | ||||||||
5 G 1,0 | 9,4 | 65.8 | 149 | ||||||
Lapp 2218070 | ÖLFLEX TRAY II CY 7 G 1,0 | ||||||||
7 G 1,0 | 10,1 | 86.9 | 193 | ||||||
Lapp 2218120 | ÖLFLEX TRAY II CY 12 G 1,0 | ||||||||
12 G 1,0 | 12,9 | 149.3 | 330 | ||||||
Lapp 2218180 | ÖLFLEX TRAY II CY 18 G 1,0 | ||||||||
18 G 1,0 | 15,7 | 214.2 | 438 | ||||||
Lapp 2218250 | ÖLFLEX TRAY II CY 25 G 1,0 | ||||||||
25 G 1,0 | 17,7 | 354.2 | 574 | ||||||
Lapp 2216030 | ÖLFLEX TRAY II CY 3 G 1,5 | ||||||||
3 G 1,5 | 8,9 | 59.8 | 144 | ||||||
Lapp 2216040 | ÖLFLEX TRAY II CY 4 G 1,5 | ||||||||
4 G 1,5 | 9,6 | 74.5 | 173 | ||||||
Lapp 2216050 | ÖLFLEX TRAY II CY 5 G 1,5 | ||||||||
5 G 1,5 | 10,3 | 93.5 | 189 | ||||||
Lapp 2216070 | ÖLFLEX TRAY II CY 7 G 1,5 | ||||||||
7 G 1,5 | 11,3 | 130.5 | 246 | ||||||
Lapp 2216120 | ÖLFLEX TRAY II CY 12 G 1,5 | ||||||||
12 G 1,5 | 15,1 | 213.8 | 426 | ||||||
Lapp 2216180 | ÖLFLEX TRAY II CY 18 G 1,5 | ||||||||
18 G 1,5 | 17,3 | 312.4 | 515 | ||||||
Lapp 2216250 | ÖLFLEX TRAY II CY 25 G 1,5 | ||||||||
25 G 1,5 | 19,6 | 415.6 | 708 | ||||||
Lapp 2214030 | ÖLFLEX TRAY II CY 3 G 2,5 | ||||||||
3 G 2,5 | 9,8 | 91.2 | 180 | ||||||
Lapp 2214040 | ÖLFLEX TRAY II CY 4 G 2,5 | ||||||||
4 G 2,5 | 10,7 | 125.7 | 223 | ||||||
Lapp 2214050 | ÖLFLEX TRAY II CY 5 G 2,5 | ||||||||
5 G 2,5 | 11,6 | 150.1 | 268 | ||||||
Lapp 2214070 | ÖLFLEX TRAY II CY 7 G 2,5 | ||||||||
7 G 2,5 | 12,5 | 201.2 | 327 | ||||||
Lapp 2214120 | ÖLFLEX TRAY II CY 12 G 2,5 | ||||||||
12 G 2,5 | 16,9 | 333.6 | 595 | ||||||
Lapp 2214180 | ÖLFLEX TRAY II CY 18 G 2,5 | ||||||||
18 G 2,5 | 19,5 | 487.6 | 784 | ||||||
Lapp 2214250 | ÖLFLEX TRAY II CY 25 G 2,5 | ||||||||
25 G 2,5 | 23,3 | 685.1 | 1048 | ||||||
Lapp 2212040 | ÖLFLEX TRAY II CY 4 G 4 | ||||||||
4 G 4 | 12,5 | 186.4 | 315 | ||||||
Lapp 2212050 | ÖLFLEX TRAY II CY 5 G 4 | ||||||||
5 G 4 | 14,4 | 232.6 | 388 | ||||||
Lapp 2212070 | ÖLFLEX TRAY II CY 7 G 4 | ||||||||
7 G 4 | 15,5 | 310.2 | 499 | ||||||
Lapp 2210040 | ÖLFLEX TRAY II CY 4 G 6 | ||||||||
4 G 6 | 15,5 | 271.7 | 552 | ||||||
Lapp 2210070 | ÖLFLEX TRAY II CY 7 G 6 | ||||||||
7 G 6 | 18,2 | 457.4 | 856 | ||||||
Lapp 2208040 | ÖLFLEX TRAY II CY 4 G 10 | ||||||||
4 G 10 | 18,7 | 438.6 | 857 | ||||||
Lapp 2206040 | ÖLFLEX TRAY II CY 4 G 16 | ||||||||
4 G 16 | 23,3 | 699.0 | 1208 | ||||||
Lapp 2204040 | ÖLFLEX TRAY II CY 4 G | ||||||||
4 G | 4 | 28,6 | 1296.8 | 1982 | |||||
Lapp 2202040 | ÖLFLEX TRAY II CY 4 G | ||||||||
4 G | 2 | 33,2 | 1899.5 | 2903 |
Application range
- Industrial machinery; plant engineering
- TC-ER (Tray Cable Exposed Run) approval for open wiring between cable tray and industrial machines/plants acc. to NEC 336.10(7)
- Wind turbines: USA Wind Turbine Tray Cable (WTTC)
- Class 1, Div. 2 in accordance with NEC “National Electrical Code” Art. 336, 392, 501
- Suitable for outdoor use and direct burial
Benefits
- Wide application range due to multiple approvals
- Cost-saving, easy installation due to omission of closed raceways (suitable for open wiring)
Product Make-up
- Fine-wire strand made of bare copper wires
- Insulation: PVC+nylon sheath (PA skin)
- Aluminum-coated foil
- Tinned-copper braiding
- Outer sheath made of special PVC compound, black
Norm references / Approvals
- Multi-standard cables have conductor strands with nominal sizes in mm² or AWG/kcmil. The master size is mentioned in the table below, while the equivalent size of the other system can be found in the Appendix T16 of this catalogue. For this related secondary size the cross-section of the conductor mostly works out to be greater than the
specified nominal value. - Approvals: UL MTW (Machine-tool Wire) [E155920]; UL AWM (Appliance Wiring Material-Component) style 20886 (+105 °C) [E100338]; UL Wet Approval 75ºC; UL Type TC (Tray Cable) -ER (Exposed Run) [E171371] or DP-1; UL PLTC (Power Limited Tray Cable) -ER (Exposed Run); UL ITC (Instrumentation Tray Cable) -ER (Exposed Run); UL WTTC (FT4) [E323700]; OIL RES. I, OIL RES. II; P-07-KA050016-MSHA (ÖLFLEX® TRAY II CY); c(UL) CIC / TC and FT4; CSA-AWM I (internal wiring)/ II (external wiring) A (dry)/ B (wet); FT4 (highly flame-retardant)
Product features
- Flame-retardant according to CSA FT4
UL Vertical-Tray Flame Test - Oil-resistant according to UL OIL RES I & II
- Water-resistant, UL Wet Approval 75 °C
- UV-resistant UL SUN RES
- Suitable for torsional applications which are typical for the loop in wind turbine generators (WTG)
Core identification code | Black with white numbers |
Classification | ETIM 5.0 Class-ID: EC000104 ETIM 5.0 Class-Description: Control cable |
Conductor stranding | Fine copper wire strands |
Torsion movement in WTG | TW-0 & TW-2, refer to Appendix T0 |
Minimum bending radius | Static/Occ. moved: 5/20xOD* |
Nominal voltage | UL/CSA: 600 V (TC, MTW, CIC), WTTC 1000 V UL/CSA: 1000 V (AWM) VDE U0 /U: 600/1000 V |
Protective conductor | G = with GN-YE protective conductor X = without protective conductor |
Temperature range | -40°C (static)/ -25°C (occ. moved) to +90°C (AWM: +105°C) |