Product Description
ÖLFLEX® CLASSIC 115 CY
ÖLFLEX® CLASSIC 400 P
ÖLFLEX® 191 CY
Screened and oil-resistant multi-standard cable with AWM approval
High electrical performance due to 4 kV test voltage; Multifunctional application possibilities
- Conductor cross-section up to 120 mm²
- Oil-resistant according to EN 50363-4-1: TM5
- Missing dimensions: See ÖLFLEX® 150 CY
SKU: 100000023
Categories: CABLES & ACCESSORIES, Power and control cables, PVC sheath - approved, Various applications
Article List
Product description
Technical Data
Lapp No. | Product Name | Datasheet / Product video | Request Quote | ||||
---|---|---|---|---|---|---|---|
Number of cores and mm² per conductor | Outer diameter (mm) | Copper index (kg/km) | Weight (kg/km) | ||||
Lapp 0011234 | ÖLFLEX 191 CY 7 G 0,75 | ||||||
7 G 0,75 | 10,5 | 85.9 | 187 | ||||
Lapp 0011202 | ÖLFLEX 191 CY 2 X 1,0 | ||||||
2 X 1,0 | 8,4 | 48.0 | 126 | ||||
Lapp 0011180 | ÖLFLEX 191 CY 3 G 1,0 | ||||||
3 G 1,0 | 8,8 | 55.8 | 122 | ||||
Lapp 0011181 | ÖLFLEX 191 CY 4 G 1,0 | ||||||
4 G 1,0 | 9,6 | 80.8 | 157 | ||||
Lapp 0011182 | ÖLFLEX 191 CY 5 G 1,0 | ||||||
5 G 1,0 | 10,3 | 89.4 | 183 | ||||
Lapp 0011183 | ÖLFLEX 191 CY 7 G 1,0 | ||||||
7 G 1,0 | 11,2 | 99.9 | 207 | ||||
Lapp 0011184 | ÖLFLEX 191 CY 12 G 1,0 | ||||||
12 G 1,0 | 14,6 | 175.7 | 342 | ||||
Lapp 0011185 | ÖLFLEX 191 CY 18 G 1,0 | ||||||
18 G 1,0 | 17.0 | 241.7 | 472 | ||||
Lapp 0011186 | ÖLFLEX 191 CY 25 G 1,0 | ||||||
25 G 1,0 | 20,1 | 341.7 | 648 | ||||
Lapp 0011302 | ÖLFLEX 191 CY 2 X 1,5 | ||||||
2 X 1,5 | 9.0 | 64.7 | 156 | ||||
Lapp 0011187 | ÖLFLEX 191 CY 3 G 1,5 | ||||||
3 G 1,5 | 9,6 | 89.1 | 166 | ||||
Lapp 0011188 | ÖLFLEX 191 CY 4 G 1,5 | ||||||
4 G 1,5 | 10,3 | 96.6 | 191 | ||||
Lapp 0011189 | ÖLFLEX 191 CY 5 G 1,5 | ||||||
5 G 1,5 | 11,3 | 111.2 | 222 | ||||
Lapp 0011190 | ÖLFLEX 191 CY 7 G 1,5 | ||||||
7 G 1,5 | 12,1 | 145.2 | 270 | ||||
Lapp 0011191 | ÖLFLEX 191 CY 12 G 1,5 | ||||||
12 G 1,5 | 16,1 | 257.0 | 464 | ||||
Lapp 0011192 | ÖLFLEX 191 CY 18 G 1,5 | ||||||
18 G 1,5 | 18,7 | 382.8 | 679 | ||||
Lapp 0011193 | ÖLFLEX 191 CY 25 G 1,5 | ||||||
25 G 1,5 | 23.0 | 546.2 | 952 | ||||
Lapp 0011194 | ÖLFLEX 191 CY 3 G 2,5 | ||||||
3 G 2,5 | 10,8 | 111.1 | 221 | ||||
Lapp 0011195 | ÖLFLEX 191 CY 4 G 2,5 | ||||||
4 G 2,5 | 11,4 | 140.6 | 269 | ||||
Lapp 0011196 | ÖLFLEX 191 CY 5 G 2,5 | ||||||
5 G 2,5 | 12,9 | 167.3 | 325 | ||||
Lapp 0011197 | ÖLFLEX 191 CY 7 G 2,5 | ||||||
7 G 2,5 | 14,1 | 240.0 | 421 | ||||
Lapp 30010542 | ÖLFLEX 191 CY 12 G 2,5 | ||||||
12 G 2,5 | 17,9 | 414.9 | 769 | ||||
Lapp 30010543 | ÖLFLEX 191 CY 18 G 2,5 | ||||||
18 G 2,5 | 22.0 | 626.1 | 1102 | ||||
Lapp 30010544 | ÖLFLEX 191 CY 4 G 4 | ||||||
4 G 4 | 13,6 | 236.7 | 462 | ||||
Lapp 30010545 | ÖLFLEX 191 CY 5 G 4 | ||||||
5 G 4 | 14,9 | 277.8 | 535 | ||||
Lapp 30010546 | ÖLFLEX 191 CY 7 G 4 | ||||||
7 G 4 | 16,2 | 393.4 | 735 | ||||
Lapp 30010548 | ÖLFLEX 191 CY 4 G 6 | ||||||
4 G 6 | 15,8 | 317.1 | 574 | ||||
Lapp 3023130 | ÖLFLEX 191 CY 5 G 6 | ||||||
5 G 6 | 17,3 | 413.7 | 737 | ||||
Lapp 30010547 | ÖLFLEX 191 CY 7 G 6 | ||||||
7 G 6 | 18,8 | 563.8 | 950 | ||||
Lapp 3023131 | ÖLFLEX 191 CY 4 G 10 | ||||||
4 G 10 | 19,5 | 550.4 | 946 | ||||
Lapp 30010639 | ÖLFLEX 191 CY 4 G 16 | ||||||
4 G 16 | 24,7 | 819.1 | 1189 | ||||
Lapp 3023132 | ÖLFLEX 191 CY 4 G 25 | ||||||
4 G 25 | 28,7 | 1165.0 | 1692 | ||||
Lapp 30010928 | ÖLFLEX 191 CY 4 G 35 | ||||||
4 G 35 | 32.0 | 1683.0 | 2700 | ||||
Lapp 3026535 | ÖLFLEX 191 CY 4 G 50 | ||||||
4 G 50 | 39,7 | 2342.0 | 3362 | ||||
Lapp 3025946 | ÖLFLEX 191 CY 4 G 70 | ||||||
4 G 70 | 44,8 | 3229.0 | 4490 | ||||
Lapp 3025947 | ÖLFLEX 191 CY 4 G 95 | ||||||
4 G 95 | 50.0 | 4010.0 | 5540 | ||||
Lapp 3026536 | ÖLFLEX 191 CY 4 G 120 | ||||||
4 G 120 | 55,4 | 5012.0 | 6960 |
Application range
- Plant engineering
Industrial machinery
Heating and air-conditioning systems - In EMC-sensitive environments
(electromagnetic compatibility) - Mainly used in dry, damp and wet interiors (including water-oil mixtures), but not for outdoor use
- For fixed installation under medium mechanical load conditions, and applications with occasional flexing at free, non-continuously recurring movement without tensile load or compulsory guidance
- Note: for the use of AWM (Appliance Wiring Material) cables in industrial machinery (USA) according to NFPA 79 Ed. 2012: please see the catalogue appendix table T29
Benefits
- High electrical performance due to 4 kV test voltage
- Multifunctional application possibilities
Product Make-up
- Fine-wire strand made of bare copper wires
- PVC core insulation
- PVC inner sheath, grey
- Tinned-copper braiding
- PVC outer sheath, high oil-resistance, grey (RAL 7001)
Norm references / Approvals
- UL AWM Style 21098 or 2587
CSA AWM I A/B II A/B - Multi-standard cables have conductor strands with nominal sizes in mm² or AWG/kcmil. The master size is mentioned in the table below, while the equivalent size of the other system can be found in the Appendix T16 of this catalogue. For this related secondary size the cross-section of the conductor mostly works out to be greater than the
specified nominal value.
Product features
- Flame-retardant according to IEC 60332-1-2
and UL 1581 §1061 Cable Flame Test - Oil-resistant according to EN 50363-4-1: TM5
- High degree of screening
low transfer impedance
(max. 250 ?/km at 30 MHz)
Core identification code | Black with white numbers acc. to VDE 0293-1 |
Classification | ETIM 5.0 Class-ID: EC000104 ETIM 5.0 Class-Description: Control cable |
Conductor stranding | Fine wire according to VDE 0295, class 5/IEC 60228 class 5 |
Minimum bending radius | Occasional flexing: 20 x outer diameter Fixed installation: 6 x outer diameter |
Nominal voltage | HAR U0/U: 300/500 V UL/CSA: 600 V |
Test voltage | 4000 V |
Protective conductor | G = with GN-YE protective conductor X = without protective conductor |
Temperature range | Occasional flexing: HAR: -5°C to +70°C UL/CSA: -5°C to +90°C Fixed installation: HAR: -40°C to +70°C UL/CSA: -40°C to +90°C |