Product Description
 
                                
                                    ÖLFLEX® ROBUST 200
                                    
				 
                                
		 	ÖLFLEX® EB CY
				 
According to DIN EN 60079-14; VDE 0165 part 1
Space-saving installation due to small cable diameters; Copper wire braid screening of the ÖLFLEX® EB CY protects signal transmission within intrinsically safe circuits against electromagnetic interference
- For use within intrinsically safe circuits
- EMC-compliant
|  |  | 
|  |  | 
	
	
		SKU: 100000017
	
	Categories: CABLES & ACCESSORIES, Intrinsically safe circuits, Power and control cables, Various applications
	
	
        	
            		                    
                
						            Article List
	
	            
	            	
		                
		            
	            
				            Product description
	
	            
	            	
		                  
		            
	            
				            Technical Data
	
	            
	            	
		                
		            
	            
							
        	 
        
        	
	
            
        | Lapp No. | Product Name | Datasheet / Product video | Request Quote | ||||
|---|---|---|---|---|---|---|---|
| Number of cores and mm² per conductor | Outer diameter (mm) | Copper index (kg/km) | Weight (kg/km) | ||||
| ÖLFLEX® EB CY screened; without inner sheath | |||||||
| Lapp 0012640 | ÖLFLEX EB CY 2 X 0,75 | ||||||
| 2 X 0,75 | 6,2 | 43.0 | 56 | ||||
| Lapp 0012641 | ÖLFLEX EB CY 3 X 0,75 | ||||||
| 3 X 0,75 | 6,5 | 52.0 | 70 | ||||
| Lapp 0012642 | ÖLFLEX EB CY 4 X 0,75 | ||||||
| 4 X 0,75 | 7.0 | 61.0 | 95 | ||||
| Lapp 0012643 | ÖLFLEX EB CY 5 X 0,75 | ||||||
| 5 X 0,75 | 7,7 | 72.0 | 108 | ||||
| Lapp 0012644 | ÖLFLEX EB CY 7 X 0,75 | ||||||
| 7 X 0,75 | 8,3 | 89.0 | 168 | ||||
| Lapp 0012645 | ÖLFLEX EB CY 12 X 0,75 | ||||||
| 12 X 0,75 | 10,9 | 138.0 | 216 | ||||
| Lapp 0012646 | ÖLFLEX EB CY 18 X 0,75 | ||||||
| 18 X 0,75 | 12,7 | 211.0 | 315 | ||||
| Lapp 0012647 | ÖLFLEX EB CY 25 X 0,75 | ||||||
| 25 X 0,75 | 14,8 | 280.0 | 435 | ||||
| Lapp 0012650 | ÖLFLEX EB CY 2 X 1,0 | ||||||
| 2 X 1,0 | 6,5 | 51.0 | 84 | ||||
| Lapp 0012651 | ÖLFLEX EB CY 3 X 1,0 | ||||||
| 3 X 1,0 | 6,8 | 62.0 | 110 | ||||
| Lapp 0012652 | ÖLFLEX EB CY 5 X 1,0 | ||||||
| 5 X 1,0 | 8,1 | 88.0 | 156 | ||||
| Lapp 0012653 | ÖLFLEX EB CY 7 X 1,0 | ||||||
| 7 X 1,0 | 8,8 | 112.0 | 192 | ||||
| Lapp 0012654 | ÖLFLEX EB CY 12 X 1,0 | ||||||
| 12 X 1,0 | 11,5 | 185.0 | 285 | ||||
| Lapp 0012655 | ÖLFLEX EB CY 18 X 1,0 | ||||||
| 18 X 1,0 | 13,9 | 268.0 | 395 | ||||
| Lapp 0012656 | ÖLFLEX EB CY 25 X 1,0 | ||||||
| 25 X 1,0 | 15,9 | 354.0 | 656 | ||||
| Lapp 0012660 | ÖLFLEX EB CY 2 X 1,5 | ||||||
| 2 X 1,5 | 7,1 | 65.0 | 87 | ||||
| Lapp 0012661 | ÖLFLEX EB CY 3 X 1,5 | ||||||
| 3 X 1,5 | 7,5 | 82.0 | 112 | ||||
| Lapp 0012662 | ÖLFLEX EB CY 5 X 1,5 | ||||||
| 5 X 1,5 | 8,9 | 119.0 | 148 | ||||
| Lapp 0012663 | ÖLFLEX EB CY 7 X 1,5 | ||||||
| 7 X 1,5 | 9,9 | 154.0 | 193 | ||||
| Lapp 0012664 | ÖLFLEX EB CY 12 X 1,5 | ||||||
| 12 X 1,5 | 13.0 | 268.0 | 365 | ||||
| Lapp 0012666 | ÖLFLEX EB CY 25 X 1,5 | ||||||
| 25 X 1,5 | 17,9 | 530.0 | 734 | ||||
Application range
- Installation of intrinsically safe circuits, where a special cable marking for hazard area type
 “i”- intrinsic safety is specified
- In EMC-sensitive environments
 (electromagnetic compatibility)
Benefits
- Space-saving installation due to small cable diameters
- Copper wire braid screening of the ÖLFLEX® EB CY protects signal transmission within intrinsically safe circuits against electromagnetic interference
Product Make-up
- Fine-wire strand made of bare copper wires
- PVC insulation LAPP P8/1
- Plastic foil wrapping
- Tinned-copper braiding
- PVC outer sheath, sky blue RAL 5015
Norm references / Approvals
- Electrical characteristics and markings on the wires and cables are according to DIN EN 60079-14 Section 12.2.2 (VDE 0165 Part 1)
- Based on EN 50525-2-51
Product features
- Flame-retardant according IEC 60332-1-2
- High degree of screening
 low transfer impedance
 (max. 250 ?/km at 30 MHz)
| Core identification code | Black with white numbers acc. to VDE 0293-1 | 
| Mutual capacitance | Core/core approx. 135 nF/km Core/screen approx. 185 nF/km | 
| Classification | ETIM 5.0 Class-ID: EC000104 ETIM 5.0 Class-Description: Control cable | 
| Inductivity | approx. 0.65 mH/km | 
| Conductor stranding | Fine wire according to VDE 0295, class 5/IEC 60228 class 5 | 
| Minimum bending radius | Occasional flexing: 20 x outer diameter Fixed installation: 6 x outer diameter | 
| Nominal voltage | U0/U: 300/500 V | 
| Test voltage | Core/core: 3000 V Core/screen: 2000 V | 
| Temperature range | Occasional flexing: -5°C to +70°C Fixed installation: -40°C to +80°C | 




 Product information (PDF)
 Product information (PDF)


 © Copyright by Pertronic. All Rights Reserved.