Product Description
X05V-K with twin colour helix insulation
Ground Straps / Flat Ground Straps
NAYY-J
Fixed installation, direct burial; PVC cable with solid aluminium conductors
- 1. re = round conductor, single-wire; 2. rm = round conductor, multi-wire; 3. sm = sector-shaped conductor
SKU: 100000186
Categories: Building Installation, CABLES & ACCESSORIES, Cables for direct burial, Power and control cables
Article List
Product description
Technical Data
Lapp No. | Product Name | Datasheet / Product video | Request Quote | ||||
---|---|---|---|---|---|---|---|
Number of cores and mm² per conductor | Outer diameter (mm) | Alu index (kg/km) | Weight (kg/km) | ||||
Lapp 1552010 | NAYY-J 4 x 35re | ||||||
4 x 35re | 29.0 | 406.0 | 1170 | ||||
Lapp 1552011 | NAYY-J 4 x 50se | ||||||
4 x 50se | 30.0 | 580.0 | 1305 | ||||
Lapp 1552012 | NAYY-J 4 x 70se | ||||||
4 x 70se | 35.0 | 812.0 | 1730 | ||||
Lapp 1552013 | NAYY-J 4 x 95se | ||||||
4 x 95se | 39.0 | 1102.0 | 2205 | ||||
Lapp 1552014 | NAYY-J 4 x 120se | ||||||
4 x 120se | 42.0 | 1392.0 | 2655 | ||||
Lapp 1552015 | NAYY-J 4 x 150se | ||||||
4 x 150se | 46.0 | 1740.0 | 3150 | ||||
Lapp 1552016 | NAYY-J 4 x 185se | ||||||
4 x 185se | 51.0 | 2146.0 | 3925 | ||||
Lapp 1552017 | NAYY-J 4 x 240se | ||||||
4 x 240se | 60.0 | 2784.0 | 4880 |
Application range
- Power and control cable for fixed installation in the following applications:
- For indoor and outdoor use
- Burial without additional, suitable underground protection according to VDE standard HD 603/VDE 0276-603 – Part 3-G (point 4) governing PVC cables for direct burial: normal minimum installation depth 0.6 m, but at least 0.8 m under roads
- In concrete with a temperature below the maximum cable operating temperature of +70 °C according to the VDE standard HD 603/VDE 0276-603 – Part 3-G (point 4) governing PVC cables for direct burial
- In water: no longer than 2 weeks at a time, maximum submersion depth 10 metres, only in static water/bodies of water without shipping traffic
Product Make-up
- Aluminium conductor
- Abbreviations “re”, “rm”, “se”, “sm”: r = round conductor form; s = sectorial conductor form; e = single-wire conductor (wire = conductor)/braided conductor class 1 according to IEC 60228/VDE 0295 for fixed, static applications; m = multi-wire conductor/braided conductor class 2 according to IEC 60228/VDE 0295 for fixed, static applications, but with a slightly lower minimum bending factor
- Core insulation: Based on PVC
- Filling compound over the core assembly
- PVC-based outer sheath
Norm references / Approvals
- HD 603/VDE 0276-603
Product features
- Flame-retardant according IEC 60332-1-2
- Maximum tensile strain for aluminium conductors during installation is 30 N/mm² according to HD 603/VDE 0276-603: Part 1 Appendix A.4.12 and Part 3-G point 4
- Current rating according to HD 603/VDE 0276-603, Part 3-G, Table 14 (buried at +20 °C ground temperature according to HD 603/VDE 0276-603, Part 3-G, point 5) for routing underground and Table 15 (in the air at an air temperature of +30 °C according to HD 603/VDE 0276-603, Part 3-G, point 5) when used outdoors; but always taking into consideration corrections/reductions to the current rating that may be necessary according to VDE 0298-4, and VDE 0298-4 (also refer to the catalogue appendix T12) for installation in and on buildings
Core identification code | According to VDE 0293-308 (table T9) |
Classification | ETIM 5.0 Class-ID: EC000057 ETIM 5.0 Class-Description: Low voltage power cable |
Conductor stranding | Single-wire |
Minimum bending radius | Fixed installation: 12 x outer diameter |
Nominal voltage | U0/U: 0.6/1.0 kV |
Test voltage | 4000 V |
Temperature range | During installation: -5°C to +50°C Fixed installation: -30°C to +70°C |