Product Description
JE-LiYCY...BD EB
EPIC® Data PROFIBUS Connectors ATEX Screw Terminals
J-H(ST)H…BD Fire Alarm Cable
Halogen-free installation cable in accordance with DIN VDE 0815 with red outer sheath
Used to meet enhanced fire protection requirements concerning protection of people and high-value property; Does not emit any toxic or corrosive gases in the event of fire and resists the spread of fire; Aluminium-laminated plastic foil static screen with tin-plated drain wire minimises the interference of high frequency, electromagnetic fields; Decoupling of circuits by means of
twisted-pair (TP) design (crosstalk effects); J-H(ST)H…BD Fire Alarm Cable is marked with the phrase Fire alarm cable at regular intervals on the sheath. It is therefore used especially for installation in fire alarm systems.
SKU: 100000285
Categories: CABLES & ACCESSORIES, Data communication systems, Halogen-free installation and fire alarm cables, Telephone cables
Article List
Product description
Technical Data
Lapp No. | Product Name | Datasheet / Product video | Request Quote | ||||
---|---|---|---|---|---|---|---|
Number of pairs and conductor diameter (mm) | Outer diameter (mm) | Copper index (kg/km) | Weight (kg/km) | ||||
J-H(ST)H…BD Fire Alarm Cable | |||||||
Lapp 30017798 | J-H(ST)H…BD Fire Alarm Cable 2 x 2 x 0,8 | ||||||
2 x 2 x 0,8 | 7.0 | 25.0 | 77 | ||||
Lapp 30017801 | J-H(ST)H…BD Fire Alarm Cable 10 x 2 x 0,8 | ||||||
10 x 2 x 0,8 | 11.3 | 106.0 | 250 |
Application range
- This halogen-free, flame-retardant installation cable with static screen is used for telephone, data and signal transmission in subscriber stations and private branch exchange construction for telephone systems
- For fixed installation on and under plaster, in dry and damp rooms
Benefits
- Used to meet enhanced fire protection requirements concerning protection of people and high-value property
- Does not emit any toxic or corrosive gases in the event of fire and resists the spread of fire
- Aluminium-laminated plastic foil static screen with tin-plated drain wire minimises the interference of high frequency, electromagnetic fields
- Decoupling of circuits by means of
twisted-pair (TP) design (crosstalk effects) - J-H(ST)H…BD Fire Alarm Cable is marked with the phrase “Fire alarm cable” at regular intervals on the sheath. It is therefore used especially for installation in fire alarm systems.
Product Make-up
- Solid bare copper conductor
- Core insulation made of special halogen-free compound
- Cores twisted into star quads,
5 star quads are twisted into a bundle,
bundles stranded in layers - Foil wrapping,
static screening made of aluminium-laminated plastic film with copper drain wire - Outer sheath made of special halogen-free compound
Outer sheath colour: flame red (RAL 3000)
Norm references / Approvals
- Based on DIN VDE 0815
Product features
- Flame-retardant according IEC 60332-1-2
- No flame-propagation according to IEC 60332-3-24 respectively IEC 60332-3-25 (Flame spread on vertical cable or wire bundle)
- Halogen-free according to EN 50267-2-1/-2
Core identification code | according to VDE 0815, refer to Appendix T10 |
Mutual capacitance | max. 120 nF/km |
Peak operating voltage | (not for power applications) 300 V |
Classification | ETIM 5.0 Class-ID: EC000829 ETIM 5.0 Class-Description: Control cable |
Coupling | K1: approx. 300 pF/100 m K9-12: approx. 100 pF/100 m |
Conductor cross-section |
0.6 mm: 0.28 mm² 0.8 mm: 0.50 mm² |
Minimum bending radius | Fixed installation: 6 x outer diameter |
Test voltage | Core/core: 800 V Core/screen: 800 V |
Loop resistance | 0.6 mm: max. 130 ohm/km 0.8 mm: max. 73.2 ohm/km |
Temperature range | Occasional flexing: -5°C to +50°C Fixed installation: -30°C to +70°C |