Product Description
UNITRONIC® ROBUST C
J-2Y(ST)Y...ST III BD
RD-Y(ST)Y
Static screened data transmission cable for control technology
In order to reduce costs, the multi-wire stranded copper cable has been provided for Maxi TERMI-POINT® connecting technology.
This wiring method (semi-automatic) considerably reduces the time and the costs required for installation; Decoupling of circuits by means of
twisted-pair (TP) design (crosstalk effects)
SKU: 100000276
Categories: CABLES & ACCESSORIES, Data communication systems, Low frequency data transmission cables, Process control cables (RD)
Article List
Product description
Technical Data
Lapp No. | Product Name | Datasheet / Product video | Request Quote | ||||||
---|---|---|---|---|---|---|---|---|---|
Number of pairs and mm² per conductor | Number of bundles | Outer diameter (mm) | Copper index (kg/km) | Weight (kg/km) | |||||
RD-Y(ST)Y grey | |||||||||
Lapp 0032470 | RD-Y(ST)Y 2 x 2 x 0,5 | ||||||||
2 x 2 x 0,5 | 6.5 | 25.0 | 65 | ||||||
Lapp 0032471 | RD-Y(ST)Y 4 x 2 x 0,5 | ||||||||
4 x 2 x 0,5 | 1 | 9.0 | 45.0 | 110 | |||||
Lapp 0032472 | RD-Y(ST)Y 8 x 2 x 0,5 | ||||||||
8 x 2 x 0,5 | 2 | 11.5 | 85.0 | 180 | |||||
Lapp 0032474 | RD-Y(ST)Y 16 x 2 x 0,5 | ||||||||
16 x 2 x 0,5 | 4 | 15.5 | 165.0 | 310 | |||||
Lapp 0032475 | RD-Y(ST)Y 24 x 2 x 0,5 | ||||||||
24 x 2 x 0,5 | 6 | 19.0 | 245.0 | 450 | |||||
Lapp 0032476 | RD-Y(ST)Y 32 x 2 x 0,5 | ||||||||
32 x 2 x 0,5 | 8 | 21.0 | 325.0 | 560 | |||||
Lapp 0032477 | RD-Y(ST)Y 48 x 2 x 0,5 | ||||||||
48 x 2 x 0,5 | 12 | 25.5 | 485.0 | 810 | |||||
RD-Y(ST)Y blue | |||||||||
Lapp 0032479 | RD-Y(ST)Y 2 x 2 x 0,5 | ||||||||
2 x 2 x 0,5 | 6.5 | 25.0 | 65 |
Application range
- RD-Y(ST)Y is used as a data transmission cable for applications such as monitoring systems and control units
- Measurement, control and regulation technology and also in control rooms of power plants and industrial facilities.
- Suitable for transmission of analog and digital signals up to a frequency of about 10 kHz
- Designed for fixed installations in enclosed rooms.
Benefits
- In order to reduce costs, the multi-wire stranded copper cable has been provided for Maxi TERMI-POINT® connecting technology.
This wiring method (semi-automatic) considerably reduces the time and the costs required for installation. - Decoupling of circuits by means of
twisted-pair (TP) design (crosstalk effects)
Product Make-up
- 7-wire bare stranded copper conductor,
core insulation made of PVC - Cores twisted into pairs,
4 pairs twisted into a bundle,
bundles in layers,
bundles labelled using numbered foil - Aluminium-laminated plastic foil static screen with tinned drain wire
- Outer sheath made of PVC
- Outer sheath colour: Grey or Blue (RAL 5015)
Norm references / Approvals
- Based on DIN VDE 0815
Product features
- Outer sheath colour: grey or
blue for intrinsically safe systems - Variant with 2 double cores twisted as star quad
Core identification code | Pair no. 1: a-conductor: blue b-conductor: red Pair no. 2: a-conductor: grey b-conductor: yellow Pair no. 3: a-core: green b-core brown Pair no. 4: a-core: white b-core black |
Mutual capacitance | At 800 Hz: ? 100 nF/km The values may be exceeded by 20 % on cables with up to 4 double cores. |
Peak operating voltage | (not for power applications) 225 V |
Classification | ETIM 5.0 Class-ID: EC000104 ETIM 5.0 Class-Description: Control cable |
Conductor resistance | (loop): ? 73.6 Ohm/km |
Cable attenuation/attenuation | At 1 kHz: approx. 1.2 dB/km At 10 kHz: approx. 2.8 dB/km |
Minimum bending radius | Occasional flexing: 15 x outer diameter Fixed installation: 7.5 x outer diameter |
Short-range crosstalk attenuation | At 10 kHz and 500 m cable length: min. 60 dB |
Test voltage | C/C: 2000 V C/S: 2000 V |
Temperature range | Occasional flexing: -5°C to +50°C Fixed installation: -40°C to +80°C |
Characteristic impedance | At 1 kHz: approx. 370 ohm At 10 kHz: approx. 130 ohm |