Product Description
J-2Y(ST)Y...ST III BD
UNITRONIC® BUS CC FD P FRNC
UNITRONIC® BUS PB TORSION
Highly flexible application
For use where the combination of a halogen-free outer sheath with properties similar to PUR and enhanced flame-retardance is required; Cables can be used for PROFIBUS-DP as well as PROFIBUS-FMS and FIP
SKU: 100000308
Categories: CABLES & ACCESSORIES, Cables for bus systems PROFIBUS-DP/FMS/FIP, Characteristic impedance: 135 - 165 ohm, Data communication systems
Article List
Product description
Technical Data
Application range
- PROFIBUS DP (in accordance with DIN 19245 and EN 50170, e.g. for SIEMENS SIMATIC® NET, also suitable for FIP – Factory Instrumentation Protocol).
Benefits
- For use where the combination of a halogen-free outer sheath with properties similar to PUR and enhanced flame-retardance is required
- Cables can be used for PROFIBUS-DP as well as PROFIBUS-FMS and FIP
Product Make-up
- PE core insulation
Norm references / Approvals
- Approval: UL type CMX in accordance with UL 444
Product features
- TORSION: for torsional stress, e.g. robot application; ± 180° per 1 m
- Halogen-free
- Flame-retardant according IEC 60332-1-2
- Based on the bit rates listed, in accordance with PNO specifications the following maximum cable lengths for a bus segment apply
(cable type A, PROFIBUS-DP):
93.75 kbit/s = 1200 m
187.5 kbit/s = 1000 m
500 kbit/s = 400 m
1.5 Mbit/s = 200 m
12.0 Mbit/s = 100 m
Mutual capacitance | (800 Hz): max. 30 nF/km |
Peak operating voltage | (not for power applications) 300 V |
Torsion movement in WTG | Max. torsion load ± 180°/m |
Minimum bending radius | Fixed installation: 4 x outer diameter Flexing: 7.5 x outer diameter |
Test voltage | 3600 V DC (3 sec.) |
Temperature range | Operating temperature: -25°C to 75°C Storage temp.: -40°C to 80°C |
Characteristic impedance | 150 ± 15 Ohm |