Product Description
ÖLFLEX® STATIC CY black
Pre-wired front plug for PLC SIMATIC® S7-400
NYCWY
Fixed installation, direct burial; PVC cable with concentric, wave-like copper conductor and cross-conductive spiral
Concentric conductor above all as PE; Easier connection due to the waveform of the concentric copper conductor
- 1. re = round conductor, single-wire; 2. rm = round conductor, multi-wire; 3. sm = sector-shaped conductor
SKU: 100000185
Categories: Building Installation, CABLES & ACCESSORIES, Cables for direct burial, Power and control cables
Article List
Product description
Technical Data
Lapp No. | Product Name | Datasheet / Product video | Request Quote | ||||
---|---|---|---|---|---|---|---|
Number of cores and mm² per conductor | Outer diameter (mm) | Copper index (kg/km) | Weight (kg/km) | ||||
Lapp 15505003 | NYCWY 2 x 10re/10 | ||||||
2 x 10re/10 | 19.0 | 312.0 | 610 | ||||
Lapp 15505263 | NYCWY 3 x 10re/10 | ||||||
3 x 10re/10 | 20.0 | 408.0 | 775 | ||||
Lapp 15505403 | NYCWY 4 x 10re/10 | ||||||
4 x 10re/10 | 21.0 | 504.0 | 897 | ||||
Lapp 15505273 | NYCWY 3 x 16re/16 | ||||||
3 x 16re/16 | 22.0 | 643.0 | 1066 | ||||
Lapp 15505413 | NYCWY 4 x 16re/16 | ||||||
4 x 16re/16 | 24.0 | 796.0 | 1250 | ||||
Lapp 15505283 | NYCWY 3 x 25rm/25 | ||||||
3 x 25rm/25 | 26.0 | 1003.0 | 1584 | ||||
Lapp 15505423 | NYCWY 4 x 25rm/16 | ||||||
4 x 25rm/16 | 28.0 | 1142.0 | 1822 | ||||
Lapp 15505303 | NYCWY 3 x 35sm/35 | ||||||
3 x 35sm/35 | 26.0 | 1402.0 | 1710 | ||||
Lapp 15505433 | NYCWY 4 x 35sm/16 | ||||||
4 x 35sm/16 | 29.0 | 1526.0 | 2146 | ||||
Lapp 15505163 | NYCWY 3 x 50sm/50 | ||||||
3 x 50sm/50 | 30.0 | 2000.0 | 2368 | ||||
Lapp 15505443 | NYCWY 4 x 50sm/25 | ||||||
4 x 50sm/25 | 33.0 | 2203.0 | 3031 | ||||
Lapp 15505453 | NYCWY 4 x 70sm/35 | ||||||
4 x 70sm/35 | 38.0 | 3082.0 | 4056 | ||||
Lapp 15505143 | NYCWY 3 x 95sm/50 | ||||||
3 x 95sm/50 | 38.0 | 3296.0 | 4256 | ||||
Lapp 15505323 | NYCWY 3 x 95sm/95 | ||||||
3 x 95sm/95 | 39.0 | 3791.0 | 4600 | ||||
Lapp 15505463 | NYCWY 4 x 95sm/50 | ||||||
4 x 95sm/50 | 43.0 | 4208.0 | 5364 | ||||
Lapp 15505153 | NYCWY 3 x 120sm/70 | ||||||
3 x 120sm/70 | 41.0 | 4236.0 | 5314 | ||||
Lapp 15505473 | NYCWY 4 x 120sm/70 | ||||||
4 x 120sm/70 | 46.0 | 5388.0 | 6748 | ||||
Lapp 15505353 | NYCWY 3 x 150sm/70 | ||||||
3 x 150sm/70 | 45.0 | 5100.0 | 6344 | ||||
Lapp 15505483 | NYCWY 4 x 150sm/70 | ||||||
4 x 150sm/70 | 51.0 | 6540.0 | 8159 | ||||
Lapp 15505173 | NYCWY 3 x 185sm/95 | ||||||
3 x 185sm/95 | 50.0 | 6383.0 | 8054 |
Application range
- Power and control cable for fixed installation in the following applications:
- For indoor and outdoor use
- Burial without additional, suitable underground protection according to VDE standard HD 603/VDE 0276-603 – Part 3-G (point 4) governing PVC cables for direct burial: normal minimum installation depth 0.6 m, but at least 0.8 m under roads
- In concrete with a temperature below the maximum cable operating temperature of +70 °C according to the VDE standard HD 603/VDE 0276-603 – Part 3-G (point 4) governing PVC cables for direct burial
- In water: no longer than 2 weeks at a time, maximum submersion depth 10 metres, only in static water/bodies of water without shipping traffic
Benefits
- Concentric conductor above all as PE
- Easier connection due to the waveform of the concentric copper conductor
Product Make-up
- Bare copper wire conductor
- Abbreviations “re”, “rm”, “se”, “sm”: r = round conductor form; s = sectorial conductor form; e = single-wire conductor (wire = conductor)/braided conductor class 1 according to IEC 60228/VDE 0295 for fixed, static applications; m = multi-wire conductor/braided conductor class 2 according to IEC 60228/VDE 0295 for fixed, static applications, but with a slightly lower minimum bending factor
- Core insulation: Based on PVC
- Filling compound over the core assembly
- Concentric, wave-like, outer conductor made of bare copper strands with inductance-reducing, cross-conductive copper bond counter spiral
- PVC-based outer sheath
Norm references / Approvals
- HD 603/VDE 0276-603 for NYCWY with 3 or 4 cores and the relevant concentric protective conductor
Product features
- Flame-retardant according IEC 60332-1-2
- Current rating according to HD 603/VDE 0276-603, Part 3-G, Table 14 (buried at +20 °C ground temperature according to HD 603/VDE 0276-603, Part 3-G, point 5) for routing underground and Table 15 (in the air at an air temperature of +30 °C according to HD 603/VDE 0276-603, Part 3-G, point 5) when used outdoors; but always taking into consideration corrections/reductions to the current rating that may be necessary according to VDE 0298-4, and VDE 0298-4 (also refer to the catalogue appendix T12) for installation in and on buildings
Core identification code | Up to 5 cores: colour-coded according to VDE 0293-308, refer to Appendix T9 |
Classification | ETIM 5.0 Class-ID: EC000057 ETIM 5.0 Class-Description: Low voltage power cable |
Conductor stranding | Single or multi-wire |
Minimum bending radius | Fixed installation: 12 x outer diameter |
Nominal voltage | U0/U: 0.6/1.0 kV |
Test voltage | 4000 V |
Temperature range | During installation: -5°C to +50°C Fixed installation: -40°C to +70°C |