Product Description
ÖLFLEX® STATIC CY black
Pre-wired front plug for PLC SIMATIC® S7-400
NYCY
Fixed installation, direct burial; PVC cable with concentric, helical copper conductor and cross-conductive spiral
Concentric conductor above all as PE
- 1. re = round conductor, single-wire; 2. rm = round conductor, multi-wire; 3. sm = sector-shaped conductor
SKU: 100000184
Categories: Building Installation, CABLES & ACCESSORIES, Cables for direct burial, Power and control cables
Article List
Product description
Technical Data
Lapp No. | Product Name | Datasheet / Product video | Request Quote | ||||
---|---|---|---|---|---|---|---|
Number of cores and mm² per conductor | Outer diameter (mm) | Copper index (kg/km) | Weight (kg/km) | ||||
Lapp 15503003 | NYCY 2 x 1,5re/1,5 | ||||||
2 x 1,5re/1,5 | 14.0 | 52.0 | 245 | ||||
Lapp 15503103 | NYCY 3 x 1,5re/1,5 | ||||||
3 x 1,5re/1,5 | 14.0 | 66.0 | 280 | ||||
Lapp 15503203 | NYCY 4 x 1,5re/1,5 | ||||||
4 x 1,5re/1,5 | 15.0 | 81.0 | 302 | ||||
Lapp 1550330 | NYCY 7 x 1,5re/2,5 | ||||||
7 x 1,5re/2,5 | 17.0 | 133.0 | 450 | ||||
Lapp 1550332 | NYCY 12 x 1,5re/2,5 | ||||||
12 x 1,5re/2,5 | 20.0 | 205.0 | 580 | ||||
Lapp 1550337 | NYCY 24 x 1,5re/6 | ||||||
24 x 1,5re/6 | 26.0 | 413.0 | 1100 | ||||
Lapp 15503113 | NYCY 3 x 2,5re/2,5 | ||||||
3 x 2,5re/2,5 | 15.0 | 104.0 | 316 | ||||
Lapp 15503213 | NYCY 4 x 2,5re/2,5 | ||||||
4 x 2,5re/2,5 | 16.0 | 128.0 | 360 | ||||
Lapp 1550350 | NYCY 7 x 2,5re/2,5 | ||||||
7 x 2,5re/2,5 | 18.0 | 200.0 | 530 | ||||
Lapp 1550355 | NYCY 16 x 2,5re/6 | ||||||
16 x 2,5re/6 | 23.0 | 451.0 | 950 | ||||
Lapp 15503223 | NYCY 4 x 4re/4 | ||||||
4 x 4re/4 | 18.0 | 200.0 | 485 | ||||
Lapp 15503233 | NYCY 4 x 6re/6 | ||||||
4 x 6re/6 | 19.0 | 297.0 | 616 |
Application range
- Power and control cable for fixed installation in the following applications:
- For indoor and outdoor use
- Burial without additional, suitable underground protection according to VDE standard HD 603/VDE 0276-603 – Part 3-G (point 4) governing PVC cables for direct burial: normal minimum installation depth 0.6 m, but at least 0.8 m under roads
- In concrete with a temperature below the maximum cable operating temperature of +70 °C according to the VDE standard HD 603/VDE 0276-603 – Part 3-G (point 4) governing PVC cables for direct burial
- In water: no longer than 2 weeks at a time, maximum submersion depth 10 metres, only in static water/bodies of water without shipping traffic
Benefits
- Concentric conductor above all as PE
Product Make-up
- Bare copper wire conductor
- Abbreviations “re”, “rm”, “se”, “sm”: r = round conductor form; s = sectorial conductor form; e = single-wire conductor (wire = conductor)/braided conductor class 1 according to IEC 60228/VDE 0295 for fixed, static applications; m = multi-wire conductor/braided conductor class 2 according to IEC 60228/VDE 0295 for fixed, static applications, but with a slightly lower minimum bending factor
- Core insulation: Based on PVC
- Filling compound over the core assembly
- Concentric, helical, outer conductor made of bare copper strands with inductance-reducing, cross-conductive copper bond counter spiral
- PVC-based outer sheath
Norm references / Approvals
- HD 603/VDE 0276-603 for NYCY with 3 or 4 cores and the relevant additional concentric protective conductor
- HD 627/VDE 0276-627 for NYCY as from 7 cores and with the additional, concentric protective conductor
Product features
- Flame-retardant according IEC 60332-1-2
- Current rating according to HD 603/VDE 0276-603, Part 3-G, Table 14 (buried at +20 °C ground temperature according to HD 603/VDE 0276-603, Part 3-G, point 5) for routing underground and Table 15 (in the air at an air temperature of +30 °C according to HD 603/VDE 0276-603, Part 3-G, point 5) when used outdoors; but always taking into consideration corrections/reductions to the current rating that may be necessary according to VDE 0298-4, and VDE 0298-4 (also refer to the catalogue appendix T12) for installation in and on buildings
Core identification code | Up to 5 cores: colour-coded according to VDE 0293-308, refer to Appendix T9 From 6 cores: black with white numbers |
Classification | ETIM 5.0 Class-ID: EC000057 ETIM 5.0 Class-Description: Low voltage power cable |
Conductor stranding | Single or multi-wire |
Minimum bending radius | Fixed installation: 12 x outer diameter |
Nominal voltage | U0/U: 0.6/1.0 kV |
Test voltage | 4000 V |
Temperature range | During installation: -5°C to +50°C Fixed installation: -40°C to +70°C |