Product Description
UNITRONIC® FD P plus
EPIC® Data PROFIBUS Connector (Optical Link Modul)
J-Y(ST)Y…LG Fire Alarm Cable
Installation cable in accordance with DIN VDE 0815 with red outer sheath
The cable is marked with the phrase Fire alarm cable at regular intervals on the sheath. It is therefore used especially for installation in fire alarm systems; Aluminium-laminated plastic foil static screen with tin-plated drain wire minimises the interference of high frequency, electromagnetic fields; Decoupling of circuits by means of
twisted-pair (TP) design (crosstalk effects)
SKU: 100000282
Categories: CABLES & ACCESSORIES, Data communication systems, Indoor cables, Telephone cables
Article List
Product description
Technical Data
Lapp No. | Product Name | Datasheet / Product video | Request Quote | ||||
---|---|---|---|---|---|---|---|
Number of pairs and conductor diameter (mm) | Outer diameter (mm) | Copper index (kg/km) | Weight (kg/km) | ||||
J-Y(ST)Y…LG Fire Alarm Cable | |||||||
Lapp 1708001 | J-Y(ST)Y…LG Fire Alarm Cable 1 x 2 x 0,8 | ||||||
1 x 2 x 0,8 | 6.0 | 11.0 | 40 | ||||
Lapp 1708002 | J-Y(ST)Y…LG Fire Alarm Cable 2 x 2 x 0,8 | ||||||
2 x 2 x 0,8 | 7.0 | 21.0 | 60 | ||||
Lapp 1708004 | J-Y(ST)Y…LG Fire Alarm Cable 4 x 2 x 0,8 | ||||||
4 x 2 x 0,8 | 9.0 | 41.0 | 100 | ||||
Lapp 1708006 | J-Y(ST)Y…LG Fire Alarm Cable 6 x 2 x 0,8 | ||||||
6 x 2 x 0,8 | 10.5 | 62.0 | 140 | ||||
Lapp 1708010 | J-Y(ST)Y…LG Fire Alarm Cable 10 x 2 x 0,8 | ||||||
10 x 2 x 0,8 | 13.5 | 102.0 | 220 | ||||
Lapp 1708020 | J-Y(ST)Y…LG Fire Alarm Cable 20 x 2 x 0,8 | ||||||
20 x 2 x 0,8 | 16.5 | 204.0 | 380 |
Application range
- This installation cable is used to transmit signals.
- For fixed installation on and under plaster, in dry and damp rooms
- For outdoor use this cable should be installed under plaster only
Benefits
- The cable is marked with the phrase “Fire alarm cable” at regular intervals on the sheath. It is therefore used especially for installation in fire alarm systems.
- Aluminium-laminated plastic foil static screen with tin-plated drain wire minimises the interference of high frequency, electromagnetic fields
- Decoupling of circuits by means of
twisted-pair (TP) design (crosstalk effects)
Product Make-up
- Solid bare copper conductor
- Core insulation made of PVC
- Cores twisted in pairs,
pairs twisted together,
foil wrapping over cable core,
static screen made of aluminium-laminated plastic film with copper drain wire - Outer sheath made of PVC
Outer sheath colour: flame red (RAL 3000)
Norm references / Approvals
- Based on DIN VDE 0815
type J-Y(ST)Y…LG
Product features
- The 2-pair version (2x2x0.8) is twisted into a star quad
- Flame-retardant according IEC 60332-1-2
Core identification code | according to VDE 0815, refer to Appendix T10 |
Peak operating voltage | (not for power applications) 300 V |
Classification | ETIM 5.0 Class-ID: EC000829 ETIM 5.0 Class-Description: Control cable |
Coupling | (800 Hz): K1: 80% ? 300 pF/100m |
Conductor cross-section in | 0.8 mm: 0.50 mm² |
Cable attenuation/attenuation | 0.8 mm: 1.1 dB/km |
Minimum bending radius | Fixed installation: 10 x outer diameter |
Test voltage | Core/core: 800 V Core/screen: 800 V |
Loop resistance | max. 73.2 Ohm/km |
Temperature range | Occasional flexing: -5°C to +50°C Fixed installation: -30°C to +70°C |